POK |
BIPOK |
TRIPOK |
|
2 inverter
contacts 5 A |
4 inverter
contacts 5 A |
6 inverter
contacts 5 A |
| DC coil control |
| Nominal voltage (Um) |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
| Woking voltage |
80% ~ 115% |
80% ~ 115% |
80% ~ 115% |
| Consumption |
2,5W |
3,0W |
3,5W |
| AC coil
control |
| Nominal voltage |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
| Woking voltage |
85% ~110% |
85% ~110% |
85% ~110% |
| Consumption |
4,0VA |
4,0VA |
5,5VA |
| Contacts |
| Number and type |
2
changeover |
4
changeover |
6
changeover |
| Max cut-out |
5A continuous |
5A continuous |
5A continuous |
| Max transient current |
100A for 10ms |
100A for 10ms |
100A for 10ms |
| Pressure of make
contact |
|
|
|
| Pressure of break
contact |
|
|
|
| Make time Un dc |
20 ms |
20 ms |
20 ms |
| Make / break Un ac |
20 ms |
20 ms |
20 ms |
| Break time Un dc |
15 ms |
15 ms |
15 ms |
| Make / break Un ac |
20 ms |
20 ms |
20 ms |
| Mechanics and environment |
| Coil-contact dielectric
strengt |
2KV for 1 min. |
2KV for 1 min. |
2KV for 1 min. |
| Contact- contact dielectric
strengt |
1KV for 1 |
1KV for 1 |
1KV for 1 |
| Isolation resistence |
>1000Mohm to 500VDC |
>1000Mohm to 500VDC |
>1000Mohm to 500VDC |
| Mechanical life |
20.000.000operations |
20.000.000operations |
20.000.000operations |
| Environmental conditions
(tropicalised version) |
P2: coil tropicalised ( 50°C with 95%
HR) |
P2: coil tropicalised ( 50°C with 95%
HR) |
P2: coil tropicalised ( 50°C with 95%
HR) |
| Vibration resistance |
5g from 10 to 55Hz |
5g from 10 to 55Hz |
5g from 10 to 55Hz |
| Shock
resistence |
20g for 11ms |
20g for 11ms |
20g for 11ms |
| Weight |
90gr. |
170gr. |
250gr. |
| Options |
|
|
|
| Accessories |
|
|
|
| |
|
|
|
|
 |
POKS |
BIPOKS |
TRIPOKS |
|
2 inverter contacts 10A |
4 inverter contacts 10A |
6 inverter contacts 10 A |
| DC coil control |
| Nominal voltage (Um) |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
| Woking voltage |
80% ~ 115% |
80% ~ 115% |
80% ~ 115% |
| Consumption |
2,5W |
3,0W |
3,5W |
| AC coil
control |
| Nominal voltage |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
| Woking voltage |
85% ~110% |
85% ~110% |
85% ~110% |
| Consumption |
4,0VA |
4,0VA |
5,5VA |
| Contacts |
| Number and type |
2
changeover |
4
changeover |
6
changeover |
| Max cut-out |
10A continuous |
10A continuous |
10A continuous |
| Max transient current |
150A for 10ms |
150A for 10ms |
150A for 10ms |
| Pressure of make
contact |
|
|
|
| Pressure of break
contact |
|
|
|
| Make time Un dc |
20 ms |
20 ms |
20 ms |
| Make / break Un ac |
20 ms |
20 ms |
20 ms |
| Break time Un dc |
15 ms |
15 ms |
15 ms |
| Make / break Un ac |
20 ms |
20 ms |
20 ms |
| Mechanics and environment |
| Coil-contact dielectric
strengt |
2KV for 1min. |
2KV for 1min. |
2KV for 1min. |
| Contact- contact dielectric
strengt |
1KV for 1 |
1KV for 1 |
1KV for 1 |
| Isolation resistence |
>1000Mohm to 500VDC |
>1000Mohm to 500VDC |
>1000Mohm to 500VDC |
| Mechanical life |
20.000.000operations |
20.000.000operations |
20.000.000operations |
| Environmental conditions
(tropicalised version) |
P2: coil tropicalised ( 50°C with 95%
HR) |
P2: coil tropicalised ( 50°C with 95%
HR) |
P2: coil tropicalised ( 50°C with 95%
HR) |
| Vibration resistance |
5g from 10 to 55Hz |
5g from 10 to 55Hz |
5g from 10 to 55Hz |
| Shock
resistence |
20g for 11ms |
20g for 11ms |
20g for 11ms |
| Weight |
90gr. |
170gr. |
250gr. |
| Options |
|
|
|
| Accessories |
|
|
|
| |
|
|
|
|
 |
DOPPIO BIPOK |
DOPPIO BIPOKS |
DOPPIO TRIPOK |
|
8 inverter contacts 5 A |
8 inverter contacts 10A |
12 inverter contacts 5A |
| DC coil control |
| Nominal voltage (Um) |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
| Woking voltage |
80% ~115% |
80% ~115% |
80% ~115% |
| Consumption |
6,0W |
6,0W |
7,0W |
| AC coil
control |
| Nominal voltage |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
12-24-48-110-125-220 |
| Woking voltage |
85% ~110% |
85% ~110% |
85% ~110% |
| Consumption |
8,0VA |
8,0VA |
11,0VA |
| Contacts |
| Number and type |
8 changeover |
8 changeover |
12 changeover |
| Max cut-out |
5A continuous |
10A continuous |
5A continuous |
| Max transient current |
100A for 10ms |
150A for 10ms |
100A for 10ms |
| Pressure of make
contact |
|
|
|
| Pressure of break
contact |
|
|
|
| Make time Un dc |
20 ms |
20 ms |
20 ms |
| Make / break Un ac |
20 ms |
20 ms |
20 ms |
| Break time Un dc |
15 ms |
15 ms |
15 ms |
| Make / break Un ac |
20 ms |
20 ms |
20 ms |
| Mechanics and environment |
| Coil-contact dielectric
strengt |
2KV for 1 min. |
2KV for 1 min. |
2KV for 1 min. |
| Contact- contact dielectric
strengt |
1KV for 1 min. |
1KV for 1 min. |
1KV for 1 min. |
| Isolation resistence |
>1000Mohm to 500Vdc |
>1000Mohm to 500Vdc |
>1000Mohm to 500Vdc |
| Mechanical life |
20.000.000 operations |
20.000.000 operations |
20.000.000 operations |
| Environmental conditions
(tropicalised version) |
P2: coil tropicalised ( 50°C with 95%HR
) |
P2: coil tropicalised ( 50°C with 95%HR
) |
P2: coil tropicalised ( 50°C with 95%HR
) |
| Vibration resistance |
5g from 10 to 55 Hz |
5g from 10 to 55 Hz |
5g from 10 to 55 Hz |
| Shock
resistence |
20g for 11 ms |
20g for 11 ms |
20g for 11 ms |
| Weight |
340gr |
340gr |
520gr |
| Options |
|
|
|
| Accessories |
|
|
|
| |
|
|
|
MONOESTÁVEIS |
 |
DOPPIO TRIPOKS |
|
| 12 inverter contacts 10A |
| DC coil control |
| Nominal voltage (Um) |
12-24-48-110-125-220 |
|
| Woking voltage |
80% ~115% |
| Consumption |
7,0W |
| AC coil
control |
| Nominal voltage |
12-24-48-110-125-220 |
|
| Woking voltage |
85% ~ 110% |
| Consumption |
11,0VA |
| Contacts |
| Number and type |
12 changeover |
|
| Max cut-out |
5A continuous |
| Max transient current |
100A for 10ms |
| Pressure of make
contact |
|
| Pressure of break
contact |
|
| Make time Un dc |
20 ms |
| Make / break Un ac |
20 ms |
| Break time Un dc |
15 ms |
| Make / break Un ac |
20 ms |
| Mechanics and environment |
| Coil-contact dielectric
strengt |
2KV for 1 min. |
|
| Contact- contact dielectric
strengt |
1KV for 1 min. |
| Isolation resistence |
>1000Mohm to 500Vdc |
| Mechanical life |
20.000.000 operations |
| Environmental conditions
(tropicalised version) |
P2: coil tropicalised ( 50°C with 95%HR
) |
| Vibration resistance |
5g from 10 to 55 Hz |
| Shock
resistence |
20g for 11 ms |
| Weight |
520gr |
| Options |
|
| Accessories |
|
| |
|